Temperature transmitter

  • 1.jpg

Guideway temperature transmitter

Guideway temperature transmitter is the input single or double channel thermal resistance, thermoco
Description

Guideway temperature transmitter is the input single or double channel thermal resistance, thermocouple signal to output isolated single or double route current or voltage signal, and improve the electrical isolation between input, output and power. Guideway temperature transmitter can be used with unit combination instrument and DCS, PLC and other systems, in petroleum, chemical, manufacturing, electric power, metallurgy and other major projects have a wide range of applications. 1, the system transmission accuracy: ±0.5%×F·S ±0.2%×F·S 2, working environment temperature: -10~55℃ 3, the measurement of thermal resistance allowed lead resistance: ≤15Ω 4, cold end compensation temperature accuracy: 1℃(preheating time 30 minutes) 5, the current output allowed external load impedance: 4-20 MA: 0~350Ω; 0-10 Ma: 0~700Ω If larger load capacity is required, please specify when ordering 6. Internal impedance during voltage output: 250Ω 7. Insulation strength between input/output/power supply/communication/double circuit: DC dc ≥2000V.dc, AC AC≥1500V.dc 8. In line with IEC61000-4-4:1995 in the third class of industrial field against electromagnetic interference requirements 9, power supply: DC: DC24V±10%V AC: AC95 ~ 265V 10, input power: 1.3 ~ 2.5W(related to the model) 11, dimension: width × height × depth: 22.5×100×115mm two, the use of environmental rail type temperature transmitter installation position shall not have strong vibration, and from the signal end, power end and space more than IEC61000-4-4: In 1995, the intensity of the third type of industrial field electromagnetic interference, and the use of the environment must not have a serious corrosive effect on metal, plastic parts of the harmful substances. 1, input signal type thermocouple: K, E, S, B, J, R, N, T thermal resistance: Pt100, Cu100, Cu50, BA1, BA2 rail type temperature transmitter users in the selection of input signal type, please inform the input signal corresponding temperature range requirements, so that the product factory to debug well. Other input and output types are specially customized; 2, single loop input z.u can have two outputs, double circuit input can only correspond to one output; 3. If the input signal of double-circuit products is different, please contact the company; Four, type spectrum

Model number



description

WD-

x

x

x

x

Guideway temperature transmitter

Input loop





The default is single loop

D




Double circuit (mutually isolated)

y.i output

1



4-20mA

2



1-5V

3



0-10mA

4



0-5V

5



0-10V

The second route output



By default, there is no second output

1


4-20mA

2


1-5V

3


0-10mA

4


0-5V

5


0-10V

Power supply mode


The default value is 220V AC

D

Dc 24V

Input signal

Thermal resistance: Pt100, Cu100, Cu50, BA1, BA2 thermocouple: K, E, S, B, J, R, N, T

Temperature range/ The corresponding output range