Silicone rubber high temperature control cable
Description
A: product features and uses
This product is suitable for the rated AC voltage of 450/750V or below mobile or fixed laying electrical instrument connection line or signal transmission, cable has good thermal stability, can maintain good electrical performance and softness in high temperature, low temperature, corrosion, suitable for metallurgy, electric power, petrochemical and other industries with mobile temperature resistance and other special requirements for use.
Two: product implementation standards
Q/HHTZH004.2
Flame retardant and fire resistance performance test GB12666-90 standard
Three: Use features
1. Rated AC voltage: U0/U 450/750KV
z.u high operating temperature: 180℃
2. z.u Low ambient temperature: silicone rubber sheath: fixed dressing -60℃, non-fixed dressing -20℃
3. The cable installation and laying temperature should not be lower than -20 ° C.
4. The allowable bending radius of the cable is 6 times of the outer diameter of the non-armored cable
Four: basic model and name
KGG | Silicone rubber insulated and sheathed control cable |
KGGR | Silicone rubber insulated and sheathed control flexible cable |
KGGP | Silicone rubber insulated and sheathed copper wire braided shielded control cable |
KGGRP | Silicone rubber insulated and sheathed copper wire braided shielded control flexible cable |
KGGRP1 | Silicone rubber insulated and tin-coated braided shielded control flexible cable |
Note: 1 If flame-retardant silicone rubber cable is required, add ZR before model;
The silicone rubber insulated nitrile sheathed cable replaces the silicone rubber insulated and sheathed heat resistant control cable in the case of a large number of cores and a large section. The application situation is similar to that of the silicone rubber sheathed cable, and the long-term use temperature is -60-105℃.
The copper wire in the conductor core can be tinned.
Five: code name and meaning
Table 2
project | Code name | description |
Flame retardant property | ZR | Flame retardant silicone rubber sheath |
Serial code | K | Control cable |
Insulating material | G | Silicone rubber |
Sheath material | G | Silicone rubber |
YVF | Nitrile polyvinyl chloride | |
Shielding material | P | Copper wire braided shielding |
P1 | Tinned copper wire shield | |
Conductor structure | A | Single conductor |
B | 7 stranded conductors | |
R | Multiple stranded conductor |
Six: main technical indicators
1. The DC resistance of the finished cable conductor (conforming to GB3956) is specified in Table 3 of Appendix A.
2.At 20 ° C, the insulation resistance shall not be less than 500MΩ/KM.
3. The finished cable is not broken down by AC 50HZ3.0KV/5min voltage test.