DisclaimerSiteMapChineseEnglish

Special cable

  • 1.jpg

Explosion proof cable for offshore oil platform

I. Overview: Offshore oil platform explosion-proof cable This product offshore oil platform with ex
Description

I. Overview:

Offshore oil platform explosion-proof cable This product offshore oil platform with explosion risk and explosion-proof requirements of higher places, used to transmit automatic control signals.

Two, use conditions and product characteristics:

① Rated voltage: AC 250V;

High working temperature of conductor core: 70℃;

③ Low ambient temperature:

Fixed laying: -20℃;

Non-fixed laying: 0℃

(4) The allowable bending radius of the cable should not be less than 8 times of the outer diameter of the cable;

⑤ The cable has the characteristics of small distribution parameters, resistance to external interference and cross-talk between lines.


Iii. Model:

1A-CKWDZ.

Iv. Scope of Specifications:

① Two-wire group: 0.5~2.5mm2

② Three-wire group: 0.75~2.5mm2

③ Four-wire group: 0.75~2.5mm2

Logarithms of: 1, 2, 3, 4, 5, 6 (7), 8, 9, 10, 11, 12, 14, 16, 19, 24, 27, 30, 37, 44, 48, 50 (pairs).

Note: Additional data is available on request.

V. Precautions for use:

(1) Try to make it free from or less affected by electrostatic and electromagnetic induction;

(2) explosion-proof type and non-explosion-proof type lines are laid separately, there should not be a wire tube or the same cable tube, should not share the same box or the same line slot, if unavoidable, must be isolated;

③ The wiring should not be damaged and protected;

(4) The grounding of the cable shield layer should be realized as a single point of grounding;

⑤ During the storage period, attention should be paid to the sealing of the finished cable head to prevent the cable head from being damp and reducing the insulation performance, affecting the use of the cable.


Message