DisclaimerSiteMapChineseEnglish

Power cable

  • 1.jpg

Fire-resistant power cable

NH-VV fire-resistant power cable Refractory power cable NH-VV features and uses: This product has
Description

NH-VV fire-resistant power cable

Refractory power cable NH-VV features and uses: This product has high fire resistance, under the direct flame combustion, in a certain period of time does not occur short circuit and short circuit fault, therefore, in the case of fire, is conducive to reduce losses, low smoke halogen-free cable belongs to the cable, especially suitable for high fire requirements of electric power, large construction, railway, ship and other industries.

Product implementation standard

Q/HHTZH009.2

Fire resistance in line with GB12666.6-90 requirements (IEC331)

1. Rated AC voltage: U0/U 0.6/1KV

2. High long-term operating temperature: flame retardant PVC J edge and sheath 70℃ and 105℃

Fluorine plastic J edge and sheathing 200℃ and 260℃

Crosslinked polyethylene J edge 90℃

Low smoke halogen-free flame retardant polyolefin 70℃

Low smoke halogen-free flame retardant crosslinked polyolefin 90℃ and 120℃

3. Low ambient temperature: flame retardant PVC sheath: fixed dressing -40℃, non-fixed dressing -15℃

Fluorine plastic J edge and sheath: fixed laying -60℃; Non-fixed laying -20℃

4. Fire resistance characteristics:

Comply with IEC331Flame temperature 750℃, combustion time 3h, cooling time 12h, additional rated voltage, additional 3A current
Conforms to GB12666.6-A classFlame temperature 950-1000℃, combustion time 90min, additional rated voltage 3A current
Conforms to GB12666.6-B classFlame temperature 750-800℃, combustion time 90min, additional rated voltage 3A current

5. The cable installation and laying temperature shall not be lower than 0 ° C

6. Recommended allowable bending radius for laying: not less than 6 times of outer diameter of non-armored cable

Armored cable shall not be less than 12 times of cable diameter

The fluorine plastic J-edge and sheathed material cable shall not be less than 8 times of the cable OD

Fire-resistant power cable

Model numberProduct M scale
NH-VVFlame retardant PVC J-rim and sheathed fire resistant control cable
NH-FFFluorine plastic J-rim and sheathed fire-resistant control cable
NH-VDVDLow smoke low halogen flame retardant polyvinyl chloride J-edge and sheathed fire-resistant control cable
NH-YDYDLow smoke halogen-free flame retardant polyolefin J-edge and sheathed fire-resistant control cable
Note: Add 22 after armored cable model


Message
Return To The Top