Fluorine plastic high temperature resistant power cable
Description
A: product features and uses
This product is suitable for rated AC voltage 0.6/1KV and below for fixed laying of transmission and distribution lines, power transmission or motor wiring, with high temperature resistance, corrosion resistance, corrosive gas, waterproof and other characteristics, high temperature environment electrical performance stability, large load, long service life, widely used in metallurgy, electric power, petrochemical, large construction, automobile manufacturing and other industries.
Two: product implementation standards
Q/HHTZH001.2
Flame retardant and fire resistance performance test GB12666-90 standard
Three: Use features
1. Rated AC voltage: U0/U 0.6/1KV
2. Fluorine plastic high temperature resistant cable high operating temperature: poly perfluorinated ethylene propylene (F46) J edge does not exceed 200℃
Soluble polytetrafluoroethylene (PFA) J edge does not exceed 260℃
3. Low ambient temperature: fluorine plastic J edge and sheath
Fixed laying -40℃, non-fixed laying -15℃
4. The cable installation and laying temperature should not be lower than 0℃ (fluorine plastic, silicone rubber and nitrile sheathed cable should not be lower than -25℃).
5. Allowable bending radius: The minimum bending radius of a single-core cable is 15 times the outer diameter of the cable
The minimum size of a multi-core cable is 10 times the outer diameter of the cable
Four: basic model and M scale (including other models of high temperature resistant cable)
Model number | Product name | The normal operating temperature is ° C |
FF46 | Fluorine plastic J-rim and sheathed power cable | - 60-200 |
FF46-22 | Fluorinated plastic J-flanged and sheathed steel tape armoured power cable | - 60-200 |
FF46P | Fluorinated plastic J-rim and sheathed copper braided shielding power cable | - 60-200 |
ZR-F46(FV) | Fluorine plastic J-edge flame retardant PVC sheathed power cable | - 40-105 |
ZR-F46-22(FV22) | Fluoro-plastic J-edge steel tape armored flame-retardant PVC sheathed power cable | - 40-105 |
ZR192-FF46 | PFAJ flanged and sheathed power cables (materials) | - 60-260 |
ZR192-FF46P | PFAJ flanged and sheathed copper braided shielded Power cable (raw material) | - 60-260 |
ZR192-FF46-22 | PFAJ flanged and sheathed steel tape armoured power cable (raw material) | - 60-260 |
YGC-F46(FG) | Fluorine plastic J edge silicone rubber sheathed power cable | - 60-180 |
YGC-F46-22(FG22) | Fluoro-plastic J-edge steel tape armored power cable with silicone rubber sheathed | - 60-180 |
YVF-F46 | Fluorinated plastic J-edge flame retardant nitrile polyvinyl chloride sheathed power cable | - 60-105 |
YVF-F46-22 | Fluoro-plastic J-edge steel tape armored flame-retardant nitrile polyvinyl chloride sheathed power cable | - 60-105 |
Note: Add R in the original model of the soft structure cable, and the copper wire in the conductor core can be tinned.
V: Code M name and meaning Table 2
Code name | Code meaning |
Serial code | slightly |
F(F46) | Polyperfluorinated ethylene propylene (F46) |
YVF | Nitrile gum |
G | Silicone rubber |
192 | PFAJ edge and sheath |
ZR(V) | Flame retardant polyvinyl chloride (flame retardant 70℃, 90℃, 105℃ three kinds) |
22 | Steel tape armor |
32 | Fine steel wire armor |
P | Copper braided shield |
R | Multiple stranded conductor |
Six: main technical indicators
1. Dc resistance of finished cable conductor (conforming to GB3956) refer to Table 1 in Appendix A.
J-edge resistance at 2.20 ℃ shall be no less than 500MΩ/KM, and J-edge resistance at 180℃ shall be no less than 10MΩ/KM
3. The finished cable is not broken down by AC 50HZ3.5KV/5min voltage test.